Selection guide

Sizing several zones

A cabinet over 1,000 liters, or one split into several compartments, is protected with several generators. Each zone gets its own; linked by a series junction, they all trigger together.

Two StickerProMaxx generators mounted in series in a large industrial cabinet

Method

Four steps

  1. Divide the enclosure into zones that are closed: each compartment separated by a partition is a zone.
  2. Measure each zone (inside width × height × depth) and calculate its volume in liters.
  3. Choose one model per zone whose maximum volume, width and height cover the zone.
  4. Link the generators in series when they protect the same volume, and lay out the detection cable above each row of equipment.

Tall cabinets: Industrial generators are approved up to 1,900 mm high, with a tolerance up to 2,100 mm (sized on actual volume). Above 2,100 mm, you create a buffer zone at the bottom : a StickerProMaxx 500 mounted vertically on a side wall, counted as 300 liters (40% derating due to vertical mounting). The remaining liters are covered by the generators at the top, all linked in series. The calculator does the math for you.

Example

1,800 × 1,200 × 400 mm cabinet

Volume1,800 × 1,200 × 400 mm = 864 liters
A single zone1 × StickerProMaxx 1000 (up to 1,200 mm wide and 1,900 mm high)
Two 600 mm compartments2 zones of 432 liters → 2 × StickerProMaxx 500, one per compartment
Detection50 cm of cable per generator above the equipment, with an extension if the row is wider

Indicative example. Always check the maximum mounting height and the tightness of each zone (0 to 2% ventilation).

Complex project?

Multiple sites, non-standard enclosures, need for a feasibility study or calculation report: support for professional projects is provided by our parent company.

Project support: aeroxsense.com

Industrial electrical cabinet protected by StickerProMaxx with a detection cable on each row

Accessories

Series mounting hardware

Each joint is made with an AX-SERIE connector crimped with the AX-SERTX tool, then protected with an AX-6ADH70 sleeve. The AX-END end-of-line cap comes factory-fitted on every generator.

AX-SERIE copper crimp connector for linking StickerProMaxx generators in series

AX-SERIE connector

Copper crimp connector: joins an extension or links several generators in series.

Coming soon

AX-6ADH70 adhesive heat-shrink sleeve to protect StickerProMaxx detection cable joints

AX-6ADH70 sleeve

Heat-shrink sleeve that insulates and protects each crimped joint.

Coming soon

AX-SERTX crimping tool for AX-SERIE connectors on StickerProMaxx detection cable

AX-SERTX crimping tool

The tool designed for AX-SERIE connectors, for a reliable joint.

Coming soon

AX-DETECT-ML heat-sensitive detection cable on a reel, sold by the meter, for StickerProMaxx automatic extinguishers

AX-DETECT-ML detection cable

Extension sold by the meter to cover a wider row or detect on every row.

Coming soon

AX-SERFLEX green 100 mm mounting cable ties, bag of 100, to secure StickerProMaxx detection cable

AX-SERFLEX cable ties

Green 100 mm cable ties, bag of 100, to secure the cable directly above the breakers.

Coming soon

StickerProMaxx AX-REPORT signaling kit: dry contact cable for power cutoff or status reporting

AX-REPORT signaling kit

Dry contact and 3 Ω resistor: power cutoff or status reporting to a control panel, BMS or PLC.

Coming soon