Selection guide
Sizing several zones
A cabinet over 1,000 liters, or one split into several compartments, is protected with several generators. Each zone gets its own; linked by a series junction, they all trigger together.

Method
Four steps
- Divide the enclosure into zones that are closed: each compartment separated by a partition is a zone.
- Measure each zone (inside width × height × depth) and calculate its volume in liters.
- Choose one model per zone whose maximum volume, width and height cover the zone.
- Link the generators in series when they protect the same volume, and lay out the detection cable above each row of equipment.
Tall cabinets: Industrial generators are approved up to 1,900 mm high, with a tolerance up to 2,100 mm (sized on actual volume). Above 2,100 mm, you create a buffer zone at the bottom : a StickerProMaxx 500 mounted vertically on a side wall, counted as 300 liters (40% derating due to vertical mounting). The remaining liters are covered by the generators at the top, all linked in series. The calculator does the math for you.
Example
1,800 × 1,200 × 400 mm cabinet
| Volume | 1,800 × 1,200 × 400 mm = 864 liters |
| A single zone | 1 × StickerProMaxx 1000 (up to 1,200 mm wide and 1,900 mm high) |
| Two 600 mm compartments | 2 zones of 432 liters → 2 × StickerProMaxx 500, one per compartment |
| Detection | 50 cm of cable per generator above the equipment, with an extension if the row is wider |
Indicative example. Always check the maximum mounting height and the tightness of each zone (0 to 2% ventilation).
Complex project?
Multiple sites, non-standard enclosures, need for a feasibility study or calculation report: support for professional projects is provided by our parent company.

Accessories
Series mounting hardware
Each joint is made with an AX-SERIE connector crimped with the AX-SERTX tool, then protected with an AX-6ADH70 sleeve. The AX-END end-of-line cap comes factory-fitted on every generator.

AX-SERIE connector
Copper crimp connector: joins an extension or links several generators in series.
Coming soon

AX-6ADH70 sleeve
Heat-shrink sleeve that insulates and protects each crimped joint.
Coming soon

AX-SERTX crimping tool
The tool designed for AX-SERIE connectors, for a reliable joint.
Coming soon

AX-DETECT-ML detection cable
Extension sold by the meter to cover a wider row or detect on every row.
Coming soon

AX-SERFLEX cable ties
Green 100 mm cable ties, bag of 100, to secure the cable directly above the breakers.
Coming soon

AX-REPORT signaling kit
Dry contact and 3 Ω resistor: power cutoff or status reporting to a control panel, BMS or PLC.
Coming soon