Ships within 2 business days · Free pickup-point delivery over €49.90 in France

Find my model

StickerProMaxx 500

Cabinet up to 500 liters
Enclosure up to 500 liters (for example 100 × 50 × 100 cm), mounted no more than 190 cm from the bottom, series mounting possible. Need more? See the StickerProMaxx 750.

  • Triggers on its own at 170 °C, within 2 to 4 seconds
  • Detection: 50 cm of heat-sensitive cable
  • No pressure, no power, no maintenance
  • 5-year warranty · EU type-examination passed (P1)

PDF data sheet · Installation instructions

Category:

Description

Description


StickerProMaxx 500: the automatic extinguisher for electrical cabinets up to 500 liters


For industrial electrical cabinets, it protects up to 500 liters and puts out a fire on its own, with no power, no pressure and no maintenance.


Power, control or automation cabinet: the StickerProMaxx 500 protects a volume of up to 500 liters, for example a 100 × 50 × 100 cm cabinet.


What it doesn’t replace: a portable extinguisher for a fire that has spread to the room, or a fire safety system where one is required.


Is it the right model?


Enclosure volume 500 liters maximum (for example 100 × 50 × 100 cm)
Mounting height 190 cm (75 in) max. from the bottom of the enclosure
Detection 50 cm of heat-sensitive cable, placed above the most exposed area
Ventilation 0 to 2%; beyond that, increase the capacity
Large volumes several generators mounted in series


Technical specifications


Model SPM-500
Housing dimensions 135 × 45 × 20.3 mm
Total weight 62.4 g
Extinguishing agent 24.4 g ± 3% (potassium and strontium salts)
Housing Flame-retardant ABS V0
Mounting double-sided adhesive and/or screws
Detection 50 cm (20 in) of heat-sensitive cable
Activation temperature 170 °C ± 10 °C, on contact with the flame
Activation time < 2 to 4 s via heat-sensitive cable
Discharge time 16 to 26 s
Operating pressure unpressurized
Fire classes B, C, E, F effective · A limited
Temperature range −30 °C to +70 °C (−22 °F to +158 °F)
Humidity · altitude 0 to 98% · 3,000 m max.
Protection IP20, indoor use


Installation in 6 steps


Electrical safety. Switch off the power before any work. The supply side of the main breaker, solar panels and batteries may remain live. If in doubt, call an electrician.


  1. Switch off the power at the breaker or main disconnect.
  2. Open the enclosure : remove the front panel or cover, or open the door.
  3. Clean the mounting surface, preferably with isopropyl alcohol.
  4. Mount it on the ceiling of the enclosure, diffuser facing down, directly above the area to protect, no more than 190 cm from the bottom. Press for 3 to 4 seconds (or fix with two screws).
  5. Lay out the 50 cm cable above the most exposed area (terminal blocks, breakers, drives), without tight bends, and check that nothing blocks the diffuser.
  6. Close up, switch the power back on and write the installation date on the warranty label.


Warranty and service life


Warranty 5 years, with compliant installation and normal use
Service life 6 years
Replacement after 5 years, or after any activation
Inspection visual, once a month


Compliance and documents


Aerosol generator, category P1 pyrotechnic firefighting device under Directive 2013/29/EU. EU type-examination (Module B) passed with notified body No. 0163 (LOM). Composition protected by a European patent. Designed and assembled in Toulouges, France. Transport: UN 3178, class 4.1, packing group III.


Data sheet · Instructions · EU declaration of conformity · Safety data sheet


Frequently asked questions


Who can install it?

The StickerProMaxx 500 mounts with no electrical wiring, but work inside an electrical cabinet must be done by a qualified person. Our support team can help you size the installation: support@stickerpromaxx.com.


My cabinet is larger than this model’s volume: what should I do?

Choose the next model up, or mount several generators in series. Our support team can carry out a feasibility study: support@stickerpromaxx.com.


Does it need maintenance?

No: it is unpressurized and maintenance-free. A simple monthly visual check is enough (housing secure, diffuser clear, detection cable intact), and you replace it after 5 years.


What happens when it activates?

The flame triggers the detection cable at 170 °C: within 2 to 4 seconds, the generator releases a condensed aerosol that puts out the fire inside the enclosure within 16 to 26 s. Then: wait, switch off the power, air out the room, clean the residue (under 1 g, non-corrosive) and replace the device.


Does the aerosol damage electrical equipment?

No. The aerosol is non-conductive and its residue is minimal and non-corrosive: it tackles an electrical (class E) fire without damaging nearby equipment.


Does it replace a fire extinguisher?

No. It automatically protects the inside of a closed enclosure. It doesn’t replace a portable extinguisher for a fire that has spread to the room, or a fire safety system where one is required.

Additional information

Weight 77,4 g
Dimensions 13,5 × 4,5 × 2,03 cm
Range

Industrial

Capacity

Cabinet up to 500 liters

Protected volume

500 liters

Detection

50 cm (20 in) of heat-sensitive cable

Mounting height

190 cm (75 in) max. from the bottom

Activation

170 °C ± 10 °C, 2 to 4 s

Warranty

5 years

Reviews

There are no reviews yet.