StickerProMaxx 50Mx
Panel with 4 rows of 13 modules, enclosure up to 50 L
4 rows of 13 modules, zone height up to 650 mm, enclosure up to 50 L, mounted no more than 65 cm from the bottom.
- Triggers on its own at 170 °C, within 2 to 4 seconds
- Detection: 135 cm of cable, 2 loops
- No pressure, no power, no maintenance
- 5-year warranty · EU type-examination passed (P1)
PDF data sheet · Installation instructions
Pack of 2: coming soon.
Description
Description
StickerProMaxx 50Mx: full panel protection, row by row
Its 135 cm of detection cable snakes above every row: wherever the fire starts, it’s detected within 2 seconds. It’s the most complete protection for an electrical panel.
With standard detection, the cable sits above the top row: a fire that starts lower down has to rise up to it. The StickerProMaxx 50Mx runs its cable above every row, so it triggers at the very first flames, wherever they appear.
What it doesn’t replace: a portable extinguisher for a fire that has spread to the room, or a fire safety system where one is required.
Is it the right model?
| Enclosure | 4 rows of 13 modules, zone height up to 650 mm |
| Enclosure volume | 50 liters maximum |
| Mounting height | 65 cm (25.6 in) max. from the bottom of the enclosure |
| Detection | 135 cm of cable, 2 loops |
| Enclosure ventilation | 0 to 2% (closed enclosure) |
Technical specifications
| Model | SPM-50MX |
| Housing dimensions | 120 × 18 × 16 mm |
| Total weight | 28.35 g |
| Extinguishing agent | 3.66 g ± 3% (potassium and strontium salts) |
| Housing | Flame-retardant ABS V0 |
| Mounting | double-sided adhesive and/or screws |
| Detection | 135 cm of cable, 2 loops |
| Activation temperature | 170 °C ± 10 °C, on contact with the flame |
| Activation time | < 2 to 4 s via heat-sensitive cable |
| Discharge time | 2 to 4 s |
| Operating pressure | unpressurized |
| Fire classes | B, C, E, F effective · A limited |
| Temperature range | −30 °C to +70 °C (−22 °F to +158 °F) |
| Humidity · altitude | 0 to 98% · 3,000 m max. |
| Protection | IP20, indoor use |
Installation in 6 steps
Electrical safety. Switch off the power before any work. The supply side of the main breaker, solar panels and batteries may remain live. If in doubt, call an electrician.
- Switch off the power at the breaker or main disconnect.
- Open the enclosure : remove the front panel or cover, or open the door.
- Clean the mounting surface, preferably with isopropyl alcohol.
- Mount it on the ceiling of the enclosure, diffuser facing down, directly above the area to protect, no more than 65 cm from the bottom. Press for 3 to 4 seconds (or fix with two screws).
- Snake the 135 cm cable above every row of breakers, without tight bends, and check that nothing blocks the diffuser.
- Close up, switch the power back on and write the installation date on the warranty label.
Warranty and service life
| Warranty | 5 years, with compliant installation and normal use |
| Service life | 6 years |
| Replacement | after 5 years, or after any activation |
| Inspection | visual, once a month |
Compliance and documents
Aerosol generator, category P1 pyrotechnic firefighting device under Directive 2013/29/EU. EU type-examination (Module B) passed with notified body No. 0163 (LOM). Composition protected by a European patent. Designed and assembled in Toulouges, France.
Data sheet · Instructions · EU declaration of conformity · Safety data sheet
Frequently asked questions
Can I install it myself?
Yes. The StickerProMaxx 50Mx mounts inside the panel in 30 seconds, with no electrical wiring at all. Switch off the power before opening the panel; if in doubt, call an electrician.
Why a cable above every row?
Because a fire that starts in a lower row takes time to reach a cable placed at the top of the panel. With 135 cm of cable spread across all 4 rows, detection happens within 2 seconds, whichever row it is.
Does it need maintenance?
No: it is unpressurized and maintenance-free. A simple monthly visual check is enough (housing secure, diffuser clear, detection cable intact), and you replace it after 5 years.
What happens when it activates?
The flame triggers the detection cable at 170 °C: within 2 to 4 seconds, the generator releases a condensed aerosol that puts out the fire inside the enclosure within 2 to 4 s. Then: wait, switch off the power, air out the room, clean the residue (under 1 g, non-corrosive) and replace the device.
Does the aerosol damage electrical equipment?
No. The aerosol is non-conductive and its residue is minimal and non-corrosive: it tackles an electrical (class E) fire without damaging nearby equipment.
Does it replace a fire extinguisher?
No. It automatically protects the inside of a closed enclosure. It doesn’t replace a portable extinguisher for a fire that has spread to the room, or a fire safety system where one is required.
Additional information
| Weight | 43,35 g |
|---|---|
| Dimensions | 12,0 × 1,8 × 1,6 cm |
| Packaging | Single unit, Pack of 2 |
| Range | Pro |
| Capacity | Panel with 4 rows of 13 modules, enclosure up to 50 L |
| Protected volume | 50 liters |
| Detection | 135 cm of cable, 2 loops |
| Mounting height | 65 cm (25.6 in) max. from the bottom |
| Activation | 170 °C ± 10 °C, 2 to 4 s |
| Warranty | 5 years |
Only logged in customers who have purchased this product may leave a review.








Reviews